MB-300-CL-1 Chlorine Transmitter
CH-2110 Chlorine transmitter
Application area :
The residual chlorine in swimming pool water, drinking water, water treatment and industrial process measurement.
| Features: |
l 144X144 microprocessor Residual Chlorine/Ozone transmitter l Waterproof & dustproof proof design, to fit wall/panel/pipe installation l The pH electrode can be connected by the transmitter to do the pH compensation for Residual Chlorine measuring l Manual/auto. temperature compensation l Equipped RS-485 MODBUS RTU protocol, it can connect to the digital system directly (MB-300-CL-1 serial only) l 2 channel isolate current DC 0/4~20mA with programable according to ppm/,mg/l, Temp (MB-300-CL-1 serial only) l Suitable for three electrode connection measurement |
| Parameters: | ||
| Measurement model | Cl/O3/pH/Temp | |
| measuring range | 0.00...100.00ppm(mg/l) sensor/0.00...14.00pH/ 0.00...10.00ppm(mg/l)depends on sensor/-30...130̊C | |
| Resolution | 0.01ppm(mg/l) /0.01pH/ 0.01ppm(mg/l) /0.1℃ | |
| accuracy(±1Digit) | ±0.5%±1Digit/±0.01pH±1Digit/±0.5%±1Digit/±0.5%±1Digit | |
| Storage temperature | -20~70℃ | |
| digital filtering | 0...60 seconds adjustable / factory setting 30 | |
| temperature compensation | Automatic recognition with Pt1000/NTC30K or manual | |
| Correction mode | Two or three-point calibration, offset correction (providing threezones Section optional) | |
| Hi/Lo Relay Output | 2 sets Hi/Lo programmable,N/OFF, 240VAC/ 0.5A Max | |
| Analog Output | 2 sets of programmable & isolate current DC 0/4-20mA withprogramable according toconcentration,pH,Temp,measurement | |
| Specifications: | ||
| AC supply | 100V~240VAC±10%,50/60Hz | |
| DC supply | 20~40VDC | |
| Temp | 0~50℃ | |
| Dimensions | 144mm×144mm×115mm(H×W×D) | |
| Protection | Correspond to IP65(NEMA 4) | |
| Installation | wall/panel/pipe mounting | |
| Cut off Dimensions | 138mm×138mm (H×W) | |
| Weight | 0.8Kg | |
- Prev:MB-300-CL Chlorine Transmitter